Remove all system power before installation, first battery then AC. (To power up, connect the AC first, then the battery.)
- Each OCM-16 module is a node in the CAN bus.
- The OCM-16 can be installed with or without an RNI. Connect 24V and CAN bus as shown in Figures 2 and 3.
- Up to 99 CAN modules, in any combination, can be connected to the CAN bus of each NIC-C.
- Each OCM-16 module is shipped with one CCS cable.
Cable connections for OCM-16 modules are shown in the following table:
Cable | Description | Part Number | Connections |
|---|---|---|---|
CCL | CAN-CABLE-Long 30 in., 6-conductor | 599-634214 | Connects P4 on RNI to first OCM-16. Also connects from OCM-16 to FCM/LCM/SCM/CSB modules (on door). |
CCS | CAN-CABLE-Short 5 ½ in., 6-conductor | 555-133539 | Connects OCM-16 modules to OCM-16 or SIM-16 modules in a single row. |
The CAN bus requires a 120Ω resistance at each end of the loop. Refer to the NIC-C Installation Instructions, P/N 315-033240 for details about CAN termination.
NOTES
- All wiring must be in accordance with Article 760 of NEC or local building codes.
- All circuits are power limited to NFPA 70 per NEC 760.
- Electrical Ratings:
Standby current: 14mA max. @ 24VDC
Active current: 200mA max. @ 24VDC - For additional information, refer to the NIC-C Installation Instructions, P/N 315- 033240.
- All wiring to TB1 must be:
- within the same room
- within 20 feet
- in rigid conduit
- Lamp test switch, ACK alarm switch, and audible device must be UL 864 listed devices.
- CAN network max. line resistance 15Ω.
- Mount the Lamp Test, Ack Alarm and Audible Device on the REMBOX2/4 front door.
- Wiring for TB1 and TB2 is 18 AWG min., 12 AWG max.
- Wiring for TB3 is 18 AWG min., 16 AWG max. Refer to the PSC-12 Installation Instructions, P/N 315- 033060, or the PSC-12M Installation Instructions, Document ID A6V12021370 for ground fault detection impedances.