FCM-6, LCM-8, and SCM-8

(Refer to Figure 7)

Installing FCM-6, LCM-8, SCM-8 Modules

1. Hold mounting bracket Model ID-MP so that the words UP are at the top.

2. Place each FCM/LCM/SCM in the desired position on the mounting bracket, aligning the two studs in the smaller holes on the bracket. Secure with a 10-32 nut on each threaded stud.

3. If all of the positions on the mounting plate are not filled with FCM/LCM/SCM modules, install a Control Module Blank Plate BCM in each of those positions by aligning the two studs in the smaller holes on the bracket and securing with a 10-32 nut on each threaded stud.

4. Position the filled mounting bracket over the two studs on the back of the inner door, so that the modules face through the opening and secure with a 10-32 nut on each threaded stud.

5. Repeat steps 1 through 4 until all FCM/LCM/SCM modules are installed.

6. Install a blank plate, Model ID-SP, in unused spaces on door and secure with 10-32 nuts. Refer to Models CAB2-BD/-RD and CAB3-BD/-RD Installation Instructions, P/N 315-033008 for more information.

CAN Sounder Board

(Refer to Figure 8)

Mounting The CSB

The CSB is normally positioned at the last FCM, LCM or SCM. If desired, multiple CSBs can be installed. The CSB mounts on the stud of the FCM/LCM/SCM module that it connects to.

1. Determine the position of the CSB on the ID-MP Mounting Plate. (This is normally at the last FCM, LCM or SCM module.)

2. If necessary, remove 10-32 nut from stud of FCM/LCM/SCM where CSB is to be mounted.

3. Place mounting hole on the CSB over stud.

4. Secure with 10-32 nut supplied with FCM/LCM/SCM.