Set the board address for each FCM/LCM/SCM using both of the ten-position rotary switches located on the back of the board (See Figure 5). Each of these addresses must be a sub-address of the NIC and must be the same as the addresses assigned in the Zeus Programming Tool. The CSB does not require address setting.

After setting the address, label each switch or LED. When viewed from the front panel of the FCM/LCM/SCM, the labels are on the left and the control switches and LEDs are on the right.

  • Refer to the Zeus configuration for the address of each module and its assigned functions.
  • Remove the label strip from its slot, and type or print a brief function identifier for each switch.
  • After completing the label strip, insert in back into its slot (See Figure 6).
FCM-6, LCM-8, SCM-8 Address Switches And Cable Connections
Inserting A Label Into the Back of the FCM-6