FCM Controls and Indicators

The FCM contains six sets of three pushbutton switches and their corresponding LEDs. Pressing any of the six ON, OFF, or AUTO switches generates a unique CAN message on the bus to the NIC that indicates which switch was pressed. A CAN message from the NIC to the FCM produces a preprogrammed output to the corresponding LED (ON, FLASHING, or OFF). An open collector is provided for connection to the CAN Sounder Board (CSB), a separate audio module. The CSB provides an audible feedback to indicate that the switch closed properly and that communication between the FCM and NIC was successful.

LCM Controls and Indicators

The LCM contains eight pairs of LEDs. A CAN message from the NIC to the LCM produces a preprogrammed output to any of the corresponding LEDs (ON, FLASHING, or OFF).

SCM Controls and Indicators

The SCM contains eight switches and eight pairs of LEDs. Each switch is associated with a pair of LEDs. Pressing of any of the eight switches generates a unique CAN message on the bus to the NIC that indicates which switch was pressed. A CAN message from the NIC to the SCM produces a preprogrammed output to the corresponding LED (ON, FLASHING, or OFF). An open collector is provided for connection to the CAN Sounder Board (CSB), a separate audio module. The CSB provides an audible feedback to indicate that the switch closed properly and that communication between the SCM and NIC was successful.

CSB Controls and Indicators

The CSB contains a sounder (buzzer) that sounds when any switch on an FCM or SCM is pressed. Only one CSB is required for audible feedback; more can be connected to increase the volume if needed.