WARNING

Remove all system power before installation, first battery then AC. (To power up, connect the AC first, then the battery.)

Electrical Connections

After you have set the HZM address, connect the field wiring. There are three basic connections to the HZM: initiating devices, DLC or FS-DLC device loop, and 24 VDC power. All terminals are power limited.

Initiating Devices

(Figures 2, 3, and 4)

The HZM supports one zone of initiating devices in either Class A or Class B. The initiating devices are connected to terminals 5–8 on the HZM terminal block. The HZM is a polarity insensitive module and terminals 1 and 2 can be connected to either line of the DLC or FS-DLC Device Loop. Figure 2 shows the Class A wiring. Figure 3 shows the Class B wiring.

HZM Initiating Devices Wiring Diagram
Class A/Style D (ULC DCLA) Installation

NOTES

  1. Wire 18 AWG minimum, 12 AWG maximum, 35 ohms Max.
  2. Supervised, power limited to NFPA 70 per NEC 760.
  3. Voltage 24VDC.
  4. Positive and negative ground fault detected at <60K ohms for terminals 5-8.
HZM Initiating Devices Wiring Diagram
Class B/Style B (ULC DCLB) Installation

NOTES

  1. Wire 18 AWG minimum, 12 AWG maximum, 35 ohms Max. (both sides)
  2. Supervised, power limited to NFPA 70 per NEC 760.
  3. Voltage 24VDC.
  4. Positive and negative ground fault detected at <60K ohms for terminals 5, 8.

Figure 4 shows the wiring for the PB-1191 beam detector. When the PB-1191 is used, the 2-position plug from jumper J1 must be removed.

Follow the steps listed below to remove the 2-position plug from J1:

a. Remove the screw from the center of the HZM plastic cover and place it to one side.
b. Remove the circuit board and locate jumper J1.
c. Remove the 2-position plug from J1.
d. Reassemble the circuit board and plastic cover using the screw that was removed in the first step.
e. Be sure to use the correct end of line device with the HZM in this configuration.

HZM Wiring Diagram For PB-1191 Installation

NOTE: Positive and negative ground fault detected at <60K ohms for terminals 5, 8.

Device Loops

(Figures 5 and 6)

The HZM communicates with the FireFinder-XLS via its DLC device loop. The device loop may be wired Class A or Class B. Figure 5 shows both wiring types. Refer to the DLC Installation Instructions, P/N 315-033090 for additional wiring information.

Do not mix wiring types; Zone 1 and Zone 2 must be the same wiring type.

HZM Device Loop Wiring Diagram For FireFinder-XLS

NOTES: CLASS A

  1. Loop resistance 50 ohms Max with 252 devices on the loop. Refer to the DLC Installation Instructions, P/N 315-033090 if the number of devices is less than 252.
  2. Wire 18 AWG minimum, 12 AWG maximum.
  3. No EOL device required.
  4. Supervised, power limited to NFPA 70 per NEC 760.
  5. Positive and negative ground fault detected at <60K ohms for terminals 5-8 on HZM.

NOTES: CLASS B

  1. Loop resistance 50 ohms Max with 252 devices on the loop. Refer to the DLC Installation Instructions, P/N 315-033090 if the number of devices is less than 252.
  2. Wire 18 AWG minimum, 12 AWG maximum.
  3. No EOL device required.
  4. No jumper required between terminal 1 and 2, terminal 3 and 4.
  5. Supervised, power limited to NFPA 70 per NEC 760.
  6. Positive and negative ground fault detected at <60K ohms for terminals 5-8 on HZM.

The HZM communicates with the FS-250 via its FS-DLC device loop. The device loop may be wired Class A or Class B. Figure 6 shows both wiring types. Refer to the FS-250 Installation, Operation and Maintenance Manual, P/N 315-049353, for additional wiring information.

HZM Device Loop Wiring Diagram For FS-250

NOTES

  1. Loop resistance 50 ohms Max with 252 devices on the loop. Refer to the FS- 250 Installation, Operation and Maintenance Manual if the number of devices is less than 252.
  2. Wire 18 AWG minimum, 12 AWG maximum.
  3. No EOL device required.
  4. When wiring Class B, no jumper required between terminal +OUT and +IN, terminal -OUT and -IN.
  5. Supervised, power limited to NFPA 70 per NEC 760.
  6. Positive and negative ground fault detected at <60K ohms for terminals 5-8 on HZM.

24 VDC Power

(Figure 7)

In a FireFinder-XLS System, the HZM receives its power from the 24 VDC power output on TB3 of the PSC-12 or PSX-12. In an FS-250 System, the HZM receives its power from the 24V power output on the control panel or auxiliary power supply. The 24 VDC power may be wired only as Class B. Since the HZM monitors the power at its screw terminals, you can star or T-tap the power connection. Refer to Figure 7 for the wiring diagram.

HZM 24 VDC Wiring Diagram

NOTES

  1. Wire 18 AWG minimum, 12 AWG maximum.
  2. No EOL device required.
  3. Supervised, power limited to NFPA 70 per NEC 760.
  4. A power supply which is resettable, power limited and UL listed for fire protective signaling use and is rated between 18.8-28.2 VDC.
  5. Positive and negative ground fault detected at <60K ohms for terminals 5-8 on HZM.

Mounting

  1. Mount the HZM in a standard two gang electrical box. The box must have a depth of at least 3½ inches.
  2. When the field wiring for the initiating devices, device loop, and 24 VDC is connected, press the HZM into the box and fasten it with the four screws provided.
  3. a dress bezel if necessary, making sure that the ALARM LED is aligned with the hole in the bezel.