NAC 1 through NAC 4 can be configured through the configuration tool as Shorting Device Inputs, i.e. for monitoring dry relay contacts. Wiring and configuration is limited to Class B and these inputs can be configured as Supervisory, Status or Trouble inputs. The input devices must be of shorting type. End of line resistor is required.
X300
Pin | Designation | Description |
|---|---|---|
1 | NAC1_+ | Positive feed for Contact Input Circuit 1 |
2 | NAC1_- | Return feed for Contact Input Circuit 1 |
3 | NAC2_+ | Positive feed for Contact Input Circuit 2 |
4 | NAC2_- | Return feed for Contact Input Circuit 2 |
Admissible cable cross-section: 1 x 12-18 AWG or 2 x 16-18 AWG
X400
Pin | Designation | Description |
|---|---|---|
1 | NAC3_+ | Positive feed for Contact Input Circuit 3 |
2 | NAC3_- | Return feed for Contact Input Circuit 3 |
3 | NAC4_+ | Positive feed for Contact Input Circuit 4 |
4 | NAC4_- | Return feed for Contact Input Circuit 4 |
Admissible cable cross-section: 1 x 12-18 AWG or 2 x 16-18 AWG