NAC 1 through NAC 4 can be configured through the configuration tool as Shorting Device Inputs, i.e. for monitoring dry relay contacts. Wiring and configuration is limited to Class B and these inputs can be configured as Supervisory, Status or Trouble inputs. The input devices must be of shorting type. End of line resistor is required.

X300

Pin

Designation

Description

1

NAC1_+

Positive feed for Contact Input Circuit 1

2

NAC1_-

Return feed for Contact Input Circuit 1

3

NAC2_+

Positive feed for Contact Input Circuit 2

4

NAC2_-

Return feed for Contact Input Circuit 2

Admissible cable cross-section: 1 x 12-18 AWG or 2 x 16-18 AWG

X400

Pin

Designation

Description

1

NAC3_+

Positive feed for Contact Input Circuit 3

2

NAC3_-

Return feed for Contact Input Circuit 3

3

NAC4_+

Positive feed for Contact Input Circuit 4

4

NAC4_-

Return feed for Contact Input Circuit 4

Admissible cable cross-section: 1 x 12-18 AWG or 2 x 16-18 AWG