A cable harness is required to connect batteries to the PAD-5-MB. The battery connector end that goes on the PAD-5-MB at X101 can only be inserted one way because it is keyed.

Battery connections are to be completed only after the whole system has been configured through jumpers and boards, and after AC has been applied.

Pin

Designation

Description

1

BAT (+)

DC 24 V feed for battery (RED WIRE)

2

BAT (-)

Return (Ground) feed for battery (BLUE WIRE)

Admissible cable cross-section: 1 x 12…18 AWG or 2 x 16…18 AWG

The hardware required to connect the batteries to the main board is in the battery kit.

The PAD-5 has an integrated intelligent charger, which displays the state of the battery charger by the state of two LEDs, H500 and H501. The following chart explains their function:

H500

H501

Mode

OFF

GREEN

Float

RED

OFF

Absorption Mode

GREEN

RED

Bulk Mode

OFF

OFF

Not charging, Battery Fault, AC fail/Brownout, or Battery Charger Fault

Normally when the battery is fully charged, only the H500 GREEN led should be on. The only time both LEDs should be off is when the PAD-5 is operating on batteries, due to an AC fault or brownout, or the NAC outputs are activated because of an ALARM. If the LEDs are out when on AC, refer to the Operator Interface (OI) for more diagnostic information from the displayed event messages.

Remember that the low battery cut-off and high temperature charger disable are not configurable or able to be disabled. They are there to keep the batteries in a safe operating zone. The PAD-5-MB will cease operating when the batteries fall below 19.3V while in AC loss or brownout. When AC is restored, the panel should recover and start charging the batteries again.

Also, if the temperature limit of the PAD-5-MB is exceeded, the battery charger will turn off to keep the batteries safe. As soon as the temperature falls below the threshold, the batteries will continue to charge. The OI will post a trouble, and when the temperature is safe, the OI will post the “OUT”.