The dedicated Auxiliary Output has a maximum output current of 3A2. The output can be used for devices such as door holders, DACT, or RDT. The output is power limited and supervised for overcurrent and direct shorting. To configure the output to shut down during AC loss to conserve battery, the configuration tool must be used.

If the output is configured to turn off on battery, then the output is used for supplementary purposes only.

The battery charger has priority over the total system current. If the batteries are drained, more current needs to go to charging the batteries. Therefore, if the NACs are configured as Auxiliary Outputs, they will be turned off while the batteries charge. The OI will display an overcurrent condition. After the batteries make it to float, the trouble will go out and the Auxiliary Outputs will return to ACTIVE. The dedicated Auxiliary Output (X800) will remain on, even if the battery charger is active. It is only NACs configured for Auxiliary Output that are affect by the battery charger priority.

2Combined Total output between all on-board NACs, Class A Expansion Module NACs, and AUX is 9A for a FP2012-U1 (300 Watt Power Supply) and 6A for a FP2011-U1 (170 Watt Power Supply).