The PAD-5-MB main board circuits X300 and X400 as four Class B NAC circuits or two Class A circuits. Configuration of Class A or B is done via the fire alarm control panel configuration tool. The NAC circuits can also be configured through the software tool for additional functions (See the Properties section)
The NAC outputs are power limited and are supervised for short-circuit, overcurrent, and open circuit. They are independently protected against direct short-circuits of the output terminals. The synchronization protocol (output pattern) is built into the unit, so no external module is needed. Synchronization on one P2 loop does not require the use of the NAC follower input. If synchronization is required across multiple P2 loops, then the NAC follower input must be used on all slave PAD-5-MB. One master is required to provide the signal for the rest of the PAD-5-MB.
All NAC circuits are configured via the configuration tool. Refer to Zeus/OI Rev. 14.01 or later, FS20/FS920 Configuration Tool Rev. 9.1.0R1 or later, or FC2005/FC901 Programming Tool. The 24K Ohm EOL resistor assembly is shipped with the panel. The PAD-5-MB has the ability to operate with EOL resistors in the range of 2.2K to 24K Ohms. These EOL values do not need to be configured with the tool. The PAD-5-MB handles them without user interaction.
The battery charger has priority over the total system current. If the batteries are drained, more current needs to go to charging the batteries. Therefore, if the NACs are configured as Auxiliary Outputs, they will be turned off while the batteries charge. The OI will display an overcurrent condition. After the batteries make it to float, the trouble will go out and the Auxiliary Outputs will return to ACTIVE. The dedicated Auxiliary Output (X800) will remain on, even if the battery charger is active. It is only NACs configured for Auxiliary Output that are affect by the battery charger priority.