The diagram below is used to locate important parts of the board and the table below identifies the relevant elements and their location on the PAD-5-MB.
Element | Des. | Function |
|---|---|---|
Fuses | F100 | 20 A fuse for battery |
Indicators | H500 | Battery Charging Status |
H501 | Battery Charging Status | |
H601 | NAC 1 STATUS | |
H602 | NAC 2 STATUS | |
H603 | NAC 3 STATUS | |
H604 | NAC 4 STATUS | |
H605 | AUX OUTPUT STATUS | |
H100 | 3.3VDC STATUS | |
H600 | MAIN MICROPROCESSOR HEARTBEAT | |
Programming | X6,X7 | DPU Address Programming Holes |
X602 | Serial Debug/Firmware Programming Port Main processor | |
X701 | Serial Debug/Firmware Programming Port P2 processor | |
Adjustment elements | S600 | Reset switch for Main Board processor |
S601 | Switch resets current state of Aux and NAC LEDs | |
S602 | Ground Fault Supervision Enable/Disable | |
Jumpers | X607 | Boot Strap Loader Enable/Disable Main processor. Run time jumper position DIS (2,3) |
X703 | Boot Strap Loader Enable/Disable P2 processor. Run time jumper position DIS (2,3) | |
X606 | Main processor Watchdog Enable/Disable. Run time jumper position EN (1,2) | |
Connector | X100 | Connector for power supply (PS1) |
X101 | Battery connection | |
X300 | NAC1,2 output | |
X400 | NAC3,4 output | |
X600 | NAC Follower Input | |
X700 | FDNet (P2) Input | |
X800 | Output DC 24 V AUX | |
X900, X901 | Expansion module connection |