The VFW41..U butterfly valves can accommodate flow in either direction.
In heating systems, the valve should preferably be installed in the return, where the seal will be exposed to lower temperatures, so extending its service life.
Warning
To avoid pressure shocks on the butterfly valve, the VFW41..U must be driven to its fully open position (either manually or via positioning signal Y1) prior to activating the pump(s).