Synco zoning - Basic Documentation - RMK770-1

Communication via the KNX bus

Product Family
Synco
Product Group
Air conditioning controller
Content Language
English
Content Type
Basic Documentation
Status
Valid
Date
2013-04-08
Document No
CE1P3127en
Download ID
A6V10088170
Stock No.
BPZ:RMK770-1
Product No.
RMK770-1

Zones and devices

Zoning on Synco is based on KNX and comprises the following zones for Synco 700 devices, RXB/RXL room controllers, RDG/RDF/RDU room thermostats, GxB181 VAV controller, AQR flush-mounted sensors, and QMX3 room units:

Designation

RMU

RMH

RMK

RMB

RMS

QAW

QAX9..

RXB/RXL

RD.. FCU

RD..VAV

GxB181..

AQR…

QMX3…

Zone address range
Geographical zone (apartm.) x x x x x x x x x x x 1…126
Geographical zone (room) x x x x x x x x 1…63
Geographical zone (subzone) x x x x x x 1…15
Time switch zone (apartment) x 1…126
Time switch zone (room) x 1…63
Time switch zone (subzone) x 1…15
Time switch slave (apartment) x x x x 1…126
Master/slave zone (apartment) x 1…126
Master/slave zone (room). x 1…63
Master/slave zone (subzone) x 1…15
QAW op.zone (apartment) X 1…126
Heat distribution zone x x x x x X 1…31
Heat distr zone source side x x x x 1…31
Heat distr zone consumer side x x x 1…31
Heat distr zone heating surface x 1…31
Heat distribution zone air heater. x 1…31
Heat distrib. zone, primary distr. x 1…31
Heat distrib. zone, primary ctrller x 1…31
Refrigeration distribution zone x x x x x 1…31
Refrig distr zone source side x x x 1…31
Refrig. distr zone consumer side x x 1…31
Refrig distr zone cooling surface x 1…31
Cold distribution zone air cooler. x 1…31
Air distribution zone x x x 1…31
Boiler sequencing zone x 1…16
DHW zone x 1…31
Holiday/special day zone x x x x x 1…31
Time switch, DHW slave x 1…31
Outside temperature zone x x x x x x x x x 1...31
Solar zone x 1...31
Wind zone x 1...31
LTE reception zone x x x 1…4095
LTE transmission zone x x x x x 1…4095

Note: x = fixed zone address (cannot be adjusted):

  • Outside temperature zone = 31

  • Subzone = 1