The "Remote reset of fault" function is used to reset Synco 700 RM… controller faults transmitted over the KNX bus requiring acknowledgement and reset to be acknowledged (and reset if "Remote reset of fault: Yes") with the OCI700.1 service tool, the RMZ792 bus operator unit, the OZW772 web server, and the OZW775 central communication unit.
RM… controllers
Main menu > Commissioning > Communication > Basic settings
Remote reset of faults for the RM… controllers
Default value: No
Setting values: No/Yes
Note
Apart from the RMH780 heating controller, all RM… controllers (including the RMH760B heating controller) incorporate the "Remote reset of faults" function.