QAW740 room unit - Basic Documentation - RMK770-1

Communication via the KNX bus

Product Family
Synco
Product Group
Air conditioning controller
Content Language
English
Content Type
Basic Documentation
Status
Valid
Date
2013-04-08
Document No
CE1P3127en
Download ID
A6V10088170
Stock No.
BPZ:RMK770-1
Product No.
RMK770-1

Setting procedure

The QAW740 room unit only contains the "Geographical zone (apartment)". The zone address can be set via the operator controls on the front of the unit.

Step

Action

Operating element
1

To access the setting mode, press the presence button for ca. 6 seconds. Letter A is displayed and the zone address can be set.

2 Set the zone address with the rotary knob.
In this example, the value is 5, thus A 5
Note: A stands for "Geographical zone (Apartment)"
3 Briefly press the presence button again to go to other settings (to set values with rotary knob, see Step 2).
4

After setting the zone address, press the presence button to exit setting mode.

Note

Zone addresses in the range 1…126 can be set for the "Geographical zone (apartment)" in the QAW740 room unit.