Network address - Basic Documentation - RMK770-1

Communication via the KNX bus

Product Family
Synco
Product Group
Air conditioning controller
Content Language
English
Content Type
Basic Documentation
Status
Valid
Date
2013-04-08
Document No
CE1P3127en
Download ID
A6V10088170
Stock No.
BPZ:RMK770-1
Product No.
RMK770-1

Network address

The network address for a full-scale KNX network consists of the area, line and device address. It reflects the exact position of a bus device in the overall network and is unique within the network.

Syntax of the network address

Syntax: Area.Line.Device

Range 0: Ex works for Synco bus devices = 0 (backbone)

Range 1...15:

Line 1...15: Ex works for Synco bus devices = 2

Device 1...255: Ex works for Synco bus devices = 255
Excepting OZW775 central communication unit = 150

Area and line address

The Synco bus devices are factory-set with the KNX-defined area and line address 0.2.

Individual address

The "individual address" (a term from the KNX world) consists of the address components area, line and device, and corresponds to the network address already defined.

Physical address

The "physical address" is another term for "individual address".

Subnetwork,
Subnetwork address

In KNX terms, a subnetwork is the same as a line. Hence, the subnetwork address consists of the address components "area" and "line".