The diagrams below show the relationship between filter settings, zone addresses and communication areas, based on the zone addresses for distribution zones.

Prerequisite: All area/line couplers and IP routers in the network must have the same filter setting.

LTE telegrams with zone addresses 1…15 are communicated only within the line, i.e. telegrams with these zone addresses are blocked.

Normal (route)

LTE telegrams with zone addresses 16…31 are communicated outside that line, i.e. telegrams with these zone addresses are routed.

Note

Zone addresses blocked by filter setting "Normal (route)" can be reused in other KNX areas and lines, but only if attribute "Normal (route)" is valid.

Route all

All LTE telegrams with zone addresses 1…31 are communicated throughout the network (no filtering).

Block all

All LTE telegrams with zone addresses 1...31 are communicated only within the line concerned.