Changeover based on calendar - Basic Documentation - RMK770-1

Communication via the KNX bus

Product Family
Synco
Product Group
Air conditioning controller
Content Language
English
Content Type
Basic Documentation
Status
Valid
Date
2013-04-08
Document No
CE1P3127en
Download ID
A6V10088170
Stock No.
BPZ:RMK770-1
Product No.
RMK770-1

Changeover source
calendar

Calendar-based changeover is configured in the "H/C changeover" function block (see the checkmark by the calendar symbol in the primary controller, RMU7x0B).

The HC changeover relay in the primary controller acts on heating/refrigeration generation which is also controlled by the primary controller.

Configuration

Main menu > Commissioning > Extra configuration > Heating/cooling ch'over

Operating line Range Factory setting
Heating/cooling acc to calendar No, yes. No

Setting values

Main menu > Commissioning > Settings > Heating/cooling ch'over

Operating line Range Factory setting
Start date heating 01.01. - 31.12. 01.10.
Start date cooling 01.01. - 31.12. 01.05.

Changeover occurs on "Start date, heating" or "Start date, cooling".