Depending on the application, the sensor is to be located as follows:
- Flow temperature control:
- In the heating flow
- Directly after the pump if the pump is located in the flow
- 1.5 to 2 m after the mixing valve if the pump is located in the return
- Limiting the return temperature:
- In the return at a location where the temperature can be correctly acquired.
The water must be well mixed where the temperature is measured.
Do not insulate the piping in the vicinity of the sensor.
Mount the sensor so that the cable does not enter from the top.
Permitted mounting positions | |
Forbidden mounting position |
Fixing
Mounting Instructions are printed on the packaging.
- Remove any paint on the pipe before fitting the clamp-on temperature sensor.
- Ensure that the sensor is fixed firmly with the supplied band.